Tests on electric and optical fibre cables under fire conditions – Test for vertical flame spread of vertically-mounted bunched wires or cables. Category B

Published By Publication Date Number of Pages
BSI 2018 20
Guaranteed Safe Checkout
Categories: ,

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. We’re here to assist you 24/7.
Email:[email protected]

This part of IEC 60332 covers category B for methods of test for the assessment of vertical flame spread of vertically-mounted bunched wires or cables, electrical or optical, under defined conditions.

This document relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 3,5 l/m of test sample. The flame application time is 40 min. The method of mounting uses the front of the standard ladder. The category is intended for general use where medium volumes of non-metallic material are required to be evaluated.

The test is intended for type approval testing. The requirements for the selection of cables for testing are given in Annex A. The flame spread is measured as the extent of damage of the cable sample. This procedure can be used to demonstrate the cable’s ability to limit flame spread.

A recommended performance requirement is given in Annex B.

NOTE

For the purposes of this document, the term “electric wire or cable” covers all insulated metallic conductor cables used for the conveyance of energy or signals.

PDF Catalog

PDF Pages PDF Title
2 undefined
5 Annex ZA(normative)Normative references to international publicationswith their corresponding European publications
7 English
CONTENTS
8 FOREWORD
10 INTRODUCTION
11 1 Scope
2 Normative references
3 Terms and definitions
12 4 Test apparatus
4.1 General
4.2 Ignition source
5 Test procedure
5.1 Test sample
5.2 Determination of the number of test pieces
13 5.3 Mounting of the test sample
5.3.1 Cables having at least one conductor above 35 mm2
14 5.3.2 Cables having conductors 35 mm2 and below and optical cables
5.4 Flame application time
6 Evaluation of test results
15 7 Performance requirements
8 Retest procedure
9 Test report
16 Figure 1 – Spaced cables mounted on the front side of the standard ladder
Figure 2 – Touching cables mounted on the front side of the standard ladder (arrays of cables in contact)
17 Annex A (normative) Guidance on cable selection for type approval testing
Table A.1 – Summary of test conditions
18 Annex B (informative) Recommended performance requirements
19 Bibliography
BS EN IEC 60332-3-23:2018